Name
Type
Values (Range)
Unit
Description
13=Move to detuning
point
BSYMM
FLOAT32
-1000.000...1000.000
mS
Symmetrical suscep-
tance of network
GSYMM
FLOAT32
-1000.000...1000.000
mS
Symmetrical conduc-
tance of network
BASYMM
FLOAT32
-1000.000...1000.000
mS
Asymmetrical suscep-
tance of network
GASYMM
FLOAT32
-1000.000...1000.000
mS
Asymmetrical conduc-
tance of network
BSYMM_REF
FLOAT32
-1000.000...1000.000
mS
Reference value of sym-
metrical susceptance of
network
GSYMM_REF
FLOAT32
-1000.000...1000.000
mS
Reference value of sym-
metrical conductance
of network
BASYMM_REF
FLOAT32
-1000.000...1000.000
mS
Reference value of
asymmetrical suscep-
tance of network
GASYMM_REF
FLOAT32
-1000.000...1000.000
mS
Reference value of
asymmetrical conduc-
tance of network
BCOIL
FLOAT32
-1000.000...1000.000
mS
Coil susceptance
GCOIL
FLOAT32
-1000.000...1000.000
mS
Coil conductance
BFIXCOIL
FLOAT32
-1000.000...1000.000
mS
Fixed parallel coil sus-
ceptance
GFIXCOIL
FLOAT32
-1000.000...1000.000
mS
Fixed parallel coil con-
ductance
GPARALLEL
FLOAT32
-1000.000...1000.000
mS
Parallel resistor conduc-
tance
I_COIL_HMI
FLOAT32
0.00...10000.00
A
Coil current value dedi-
cated for HMI purposes
(depends on Resonance
curve Cur setting)
I_COIL
FLOAT32
0.00...10000.00
A
Adjustable arc suppres-
sion coil value
CALIB_O_MIN
FLOAT32
0...3000
ohm
Low end switch posi-
tion of the coil (ohms)
CALIB_O_MAX
FLOAT32
0...3000
ohm
High end switch posi-
tion of the coil (ohms)
B_RATIO
FLOAT32
0.000...100.000
Susceptance ratio
PASANCR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
9.11.12
Technical data
Table 1598: PASANCR Technical data
Characteristic
Value
Measuring accuracy
Resistance:
±2% or ±1 Ω
Operation accuracy
1
I_C_NETWORK:
Control functions
1MRS759142 F
1756
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......