LVRTPTUV Output signals
Table 855: LVRTPTUV Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.5.8.8
LVRTPTUV Settings
Table 856: LVRTPTUV Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Voltage start value 0.05...1.20
xUn
0.01
0.90
Voltage value be-
low which function
starts
Table 857: LVRTPTUV Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start pha-
ses
4=Exactly 1 of 3
5=Exactly 2 of 3
6=Exactly 3 of 3
4=Exactly 1 of 3
Number of faulty
phases
Voltage selection
1=Highest Ph-to-E
2=Lowest Ph-to-E
3=Highest Ph-to-Ph
4=Lowest Ph-to-Ph
5=Positive Seq
4=Lowest Ph-to-Ph Parameter to select
voltage for curve
monitoring
Active coordinates
1...10
1
3
Coordinates used
for defining LVRT
curve
Voltage level 1
0.00...1.20
xUn
0.01
0.20
1st voltage coordi-
nate for defining
LVRT curve
Voltage level 2
0.00...1.20
xUn
0.01
0.80
2nd voltage coordi-
nate for defining
LVRT curve
Voltage level 3
0.00...1.20
xUn
0.01
0.90
3rd voltage coordi-
nate for defining
LVRT curve
Voltage level 4
0.00...1.20
xUn
0.01
0.90
4th voltage coordi-
nate for defining
LVRT curve
Voltage level 5
0.00...1.20
xUn
0.01
0.90
5th voltage coordi-
nate for defining
LVRT curve
Voltage level 6
0.00...1.20
xUn
0.01
0.90
6th voltage coordi-
nate for defining
LVRT curve
Voltage level 7
0.00...1.20
xUn
0.01
0.90
7th voltage coordi-
nate for defining
LVRT curve
Voltage level 8
0.00...1.20
xUn
0.01
0.90
8th voltage coordi-
nate for defining
LVRT curve
Table continues on the next page
Protection functions
1MRS759142 F
906
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......