settable
Coordination time, and if no block signal is received from the remote
terminal. To prevent a false trip in case of external faults, the
CR_BLOCKING
signal
must be received before the
Coordination time has elapsed. The start signal from
the overreaching residual overcurrent function DEFLPDEF is connected to the
CACC
input.
The
Coordination time setting in the blocking scheme depends, for
example, on the communication system delay and on the terminal's
response times in transmitting a
CS_BLOCKING
signal to the other feeder
end. The
Coordination time setting must not be zero.
Activating the
BLOCK
input totally blocks the directional comparison blocking
scheme. The
CS_PRM
and
OPERATE
outputs can be blocked by the
BLK_CS_OPR
input.
In
, in case of internal faults, the
CS_BLOCKING
signal is not sent as the
fault is not seen by the reverse-looking overreaching function.
~
~
DEFL_START
(Forward)
TRIP_CB_A
TRIP_CB_B
DEFL_START
(Forward)
Bus A
Bus B
3
3
Figure 714: Simplified functional diagram of the blocking scheme, internal fault
, in case of external faults, the protection relay at bus B sees the fault
in the reverse direction and sends a blocking signal
CS_BLOCKING
to the protection
relay at bus A. There is no CB operation at either end.
Protection related functions
1MRS759142 F
1256
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......