
Switch-onto-fault (SOTF) logic module enabling requires connection of
breaker close command into input
CB_CL_CMD
. Switch-onto-fault (SOTF)
logic module can be disabled by not connecting the breaker close
command signal to IFPTOC.
In case SOTF condition is detected, then all other functionality of IFPTOC
function is blocked.
Setting
SOTF Cond duration must be set higher than SOTF operate
time + SOTF reset time. SOTF functionality is reset after SOTF Cond
duration expires or at least when earth-fault detection signal deactivates
(
EF_IND
).
SOTF logic is not activated in case earth fault is detected (
EF_IND =
TRUE
) before breaker close command (input
CB_CL_CMD
is activated).
For the SOTF module typically longer reset time is needed to prevent unwanted
function reset between the current spikes during intermittent earth fault, setting
SOTF reset time. Recommended setting value is between 300-500 ms.
Applicable settings for the SOTF-module are:
Enable SOTF mode, SOTF Cond
duration, SOTF operate time and SOTF reset time.
Note that setting
CB Delay comp (circuit breaker delay compensation) is not
applicable in definite time operation, but it must be taken into account in setting
SOTF operate time.
Faulted phase identification
The faulted phase selection module provides information about the faulted phase
(A, B or C) during a single-phase earth fault.
The faulted phase is identified by monitoring the “phase-wise” fault current
estimators as follows:
(Equation 138)
(Equation 139)
(Equation 140)
Maximum value indicates the faulted phase. Actual implementation utilizes
Cumulative Phasor Summing (CPS) together with admittance calculation.
Faulted phase is available in Recorded data as
Faulted phase. In
Monitored data faulted phase is given in
FAULT_PHASE
.
Protection functions
1MRS759142 F
634
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......