11
General function block features
11.1
Definite time characteristics
11.1.1
Definite time operation
The DT mode is enabled when the
Operating curve type setting is selected either
as "ANSI Def. Time" or "IEC Def. Time". In the DT mode, the
OPERATE
output of the
function is activated when the time calculation exceeds the set
Operate delay time .
The user can determine the reset in the DT mode with the
Reset delay time setting,
which provides the delayed reset property when needed.
The
Type of reset curve setting has no effect on the reset method when
the DT mode is selected, but the reset is determined solely with the
Reset delay time setting.
The purpose of the delayed reset is to enable fast clearance of intermittent faults,
for example self-sealing insulation faults, and severe faults which may produce high
asymmetrical fault currents that partially saturate the current transformers. It is
typical for an intermittent fault that the fault current contains so called drop-off
periods, during which the fault current falls below the set start current, including
hysteresis. Without the delayed reset function, the operate timer would reset
when the current drops off. In the same way, an apparent drop-off period of the
secondary current of the saturated current transformer can also reset the operate
timer.
General function block features
1MRS759142 F
1858
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......