
If the input
GEN_MOD_LOC
is 1, indicating that the generator is in local mode, then
the Fueling fault detection module is disabled. If the quality status of the local
active power input is faulty, then the module is disabled and
INT_BLKD
output is
activated.
If one of the generators present in the same subnetwork is faulty, then that
generator is removed from comparison in the Fueling fault detection module.
The input
ENG_LOD_UNLD
suggests whether the engine is in loading or unloading
condition. When the engine is in loading condition (confirmed by GCB position
change from open to close) the fueling fault detection is disabled until the
generated power reaches 80% of the average loading of generators in the same
subnetwork or until the elapsing of
Disable time, whichever is faster. When the
function is in unloading condition (i.e. GCB continues to remain in closed position),
then the module is blocked until the elapsing of
Disable time. As the GCB status
change and
ENG_LOD_UNLD
input may not come together, by using settings (
Wait
time signal status - Wait time for Load/Unload signal and Wait time status signal
- Wait time for GCB status and Load/Unload signal) the confirmation of loading/
unloading of engine is done.
Correlation algorithm:
The Correlation algorithm compares the active power of the local generator, to its
expected behavior in the current governor mode.
The algorithm can be disabled through the setting
Disable Fuel Crl.
The function has 8 active power inputs,
P1 … P8
. The input
corresponding to the setting
Local generator Num, would be considered
as the local active power.
For example, if
Local generator Num is set to “1”, then
P1
is considered as
the local generator active power output.
Correlation algorithm uses different criteria based on the governor mode.
The governor mode information is obtained through the four binary inputs
GOV_MOD_ISOC, GOV_MOD_DRP, GOV_MOD_CDRP
and
GOV_MOD_BASE
. The governor
and AVR modes of other generators are obtained through inputs
GEN1_DATA …
GEN8_DATA
. In case any generator in the same subnetwork is communicated to be
faulty, through the inputs
GEN1_DATA … GEN8_DATA
, then that generator is not
considered in the Correlation algorithm.
If the input
GOV_MOD_ISOC
is active, the function monitors the system frequency
and active power of all generators in the same subnetwork and with the same
governor mode. If the frequency of the network exceeds the set
Expected frequency
over and above the margin
Max Freq Dev Isoc, and if the local active power is more
than the rest of the generators by a margin
Max P Dev Crl, then the generator is
deemed faulty and
OV_FUEL_FLT
output is activated.
If the frequency of the network is below the set
Expected frequency over and
above the margin
Max Freq Dev Isoc, and if the local active power is less than the
rest of the generators by a margin
Max P Dev Crl, then the generator is deemed
faulty and
UN_FUEL_FLT
output is activated. The fueling fault detection algorithm
in isochronous mode needs at least 2 generators in parallel and operating in same
mode.
When the input
GOV_MOD_DRP
is active, the function compares the local active
power and system frequency with the set droop curve. Deviation above or below
this curve (for over and under fueling conditions respectively) by a margin greater
than
Max Freq deviation, indicates a failure of the governor or the fuel system. The
Condition monitoring functions
1MRS759142 F
1410
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......