Table 36: Protocol control in the protection relay
Parameter
Options
Description
Configuration/Communication/Proto-
cols/Network1/FTP
Off
Denies FTP and FTPS
On
Allows FTP and FTPS
Secure (Default)
Allows FTPS only
Configuration/Communication/Proto-
cols/Network2/FTP
Off
Denies FTP and FTPS
On
Allows FTP and FTPS
Secure (Default)
Allows FTPS only
Configuration/Communication/Proto-
cols/HMI Port/FTP
Off
Denies FTP and FTPS
On
Allows FTP and FTPS
Secure (Default)
Allows FTPS only
Configuration/Communication/Proto-
cols/Network1/HTTPS
Off
Denies HTTPS
On (Default)
Allows HTTPS
Configuration/Communication/Proto-
cols/Network2/HTTPS
Off
Denies HTTPS
On (Default)
Allows HTTPS
Configuration/Communication/Proto-
cols/Network1/MMS
Off
Denies IEC 61850 MMS
On (Default)
Allows IEC 61850 MMS
Configuration/Communication/Proto-
cols/Network2/MMS
Off
Denies IEC 61850 MMS
On (Default)
Allows IEC 61850 MMS
Configuration/Communication/Proto-
cols/HMI Port/MMS
Off
Denies IEC 61850 MMS
On (Default)
Allows IEC 61850 MMS
Configuration/Communication/Proto-
cols/Network1/DNP
Off
Denies DNP3
On (Default)
Allows DNP3
Configuration/Communication/Proto-
cols/Network2/DNP
Off
Denies DNP3
On (Default)
Allows DNP3
Configuration/Communication/Proto-
cols/Network1/Modbus
Off
Denies Modbus
On (Default)
Allows Modbus
Configuration/Communication/Proto-
cols/Network2/Modbus
Off
Denies Modbus
On (Default)
Allows Modbus
Configuration/Communication/Proto-
cols/Network1/ IEC-60870-5-104
Off
Denies IEC 60870-5-104
On (Default)
Allows IEC 60870-5-104
Configuration/Communication/Proto-
cols/Network2/ IEC-60870-5-104
Off
Denies IEC 60870-5-104
On (Default)
Allows IEC 60870-5-104
3.2.6.3
Protocol write access rights
Write access rights are configurable for FTP, MMS, and HTTPS protocols in
Configuration > Authorization. The write access parameters are used to narrow
down services that allow setting changes on different network interfaces. Disabling
the FTP and IEC 61850 MMS write access on Network 1 and 2 prevents the user
from updating the configuration to the protection relay from PCM600. Disabling the
HTTPS write access prevents the user from writing setting changes from WHMI.
Basic functions
1MRS759142 F
88
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......