Figure 346: Permissible time-touch voltage characteristics given in standard
IEEE80 (metal-to-metal contact)
• This operation mode can be also used when maximum allowed earth potential
rise vs. operation speed follows a relationship such as 750 V/√
t[sec].
• Time margin for practical circuit-breaker operate time can be applied with
setting
CB delay Comp. Default setting is 0 ms.
•
START
and
ST_EF
outputs are activated when estimated effective earth-fault
current magnitude (considering the effect of settings
Reduction factor and
Enable harmonics) exceeds setting EF current Str Val and earth fault is detected,
and earth-fault current estimate is validated. Note that
Ena RF Compensation =
“Enable” does not affect this start condition. It is important to set setting
EF
current Str Val according to required protection sensitivity.
•
OPERATE
and
OP_EF
-outputs are activated so that the operate time is according
to the touch voltage requirements defined in standard IEEE80. i.e. operate time
is inversely proportional to the estimated fault current.
• Reset timer is started if any of the above conditions for
START
is not anymore
valid.
START
and
ST_EF
outputs stay activated until the reset timer expires
(setting
Reset delay time). After
OPERATE
output activation,
START
,
ST_EF
,
OPERATE
and
OP_EF
outputs are reset immediately i.e. reset delay time is no
longer valid.
• During re-striking/intermittent earth faults, the very high current transient may
result to very fast operation times. In case longer operation during re-striking/
intermittent earth faults is preferred and operation should be based preferably
on counted number of transients, then setting
Reset delay time should be
set to low value, say 20-40 ms. Dedicated intermittent earth-fault protection
functionality based on counted number of transients is described in
4.2.10.5.6 Intermittent earth-fault protection
.
• Applicable settings are:
Reduction factor, EF current Str Val, CB delay Comp, IEEE
multiplier, Maximum earthing Ris, IDMT stage Min Op Tm, IDMT stage Max Op
Tm, Reset delay time.
According to the standard IEEE80, the values of the permissible touch voltage
U
Tp
as a function of the fault duration
t
f
are defined as follows:
For body weight of 50kg:
(Equation 122)
1MRS759142 F
Protection functions
REX640
Technical Manual
607
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......