BLOCK
input activation resets all outputs.
Lockout handling
Function can be set to lockout state by activation of
ACT_LKOUT
input. When
function is in lockout, this is shown with
LOCKOUT
output. Lockout state can be
reset with
RST_LKOUT
input or via clear menu parameter
HSABTC reset lockout.
Lockout state can be activated also when circuit breaker decoupling, CB_DECOUPL,
activates.
Fast transfer evaluation
This module evaluates fast transfer readiness. Fast transfer is allowed if following
conditions are met:
• U_STDBY_FAIL is FALSE
Stand-by feeder voltage is greater than setting
Min standby voltage
• U_BB_FAIL is FALSE
Busbar voltage is greater than setting
Min busbar voltage
• FRQ_DIFF_FAIL is FALSE
Frequency difference between standby feeder and busbar is less than setting
Max frequency Diff
• ANG_DIFF_FAIL is FALSE
Phase angle difference is inside sector defined by
Maximum phase lead and
Maximum phase lag
• GRAD_FAIL is FALSE
Frequency rate of change in busbar is less than setting
Max DfDt
•
BLOCK
input is FALSE
•
TRANSFER_ON
input is TRUE
•
DISA_INIT
input is FALSE
• LOCKOUT is FALSE (Function is not in lockout)
• Transfer is allowed to one direction, i.e. TR_1_2_OK or TR_2_1_OK is true
If all conditions are met, then the information is signaled to Bus transfer with
FAST_READY signal.
Transfer evaluation
This module evaluates the transfer enable signal. The
READY
output is active if
following conditions are fulfilled:
• U_STDBY_FAIL is FALSE
Stand-by feeder voltage is greater than setting
Min standby voltage
•
BLOCK
input is FALSE
•
TRANSFER_ON
input is TRUE
•
DISA_INIT
input is FALSE
• LOCKOUT is FALSE
• Transfer is allowed to one direction, i.e. TR_1_2_OK or TR_2_1_OK is true
When function is ready for transfer, this is shown with output
READY
. If transfer
initiation is not possible, then
NOT_READY
output is activated.
1MRS759142 F
Control functions
REX640
Technical Manual
1767
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......