
operate with the maximum load current. The settings for all three stages are as in
.
For the application point of view, the suitable setting for instantaneous stage (I>>>)
in this example is 3 500 A (5.83 × I
2n
). I
2n
is the 1.2 multiple with nominal primary
current of the CT. For the CT characteristics point of view, the criteria given by
the current transformer selection formula is fulfilled and also the protection relay
setting is considerably below the F
a
. In this application, the CT rated burden could
have been selected much lower than 10 VA for economical reasons.
12.1.2
Current transformer requirements for transformer
differential protection
The more important the object to be protected, the more attention has to be paid
to the current transformers. It is not normally possible to dimension the current
transformer so that they repeat the currents with high DC components without
saturating when the residual flux of the current transformer is high. TR2PTDF
and TR3PTDF operate reliably even though the current transformers are partially
saturated.
The accuracy class recommended for current transformers to be used with TR2PTDF
and TR3PTDF is 5P or X-type. In the 5P type, the limit of the current error at the
rated primary current is 1 percent and the limit of the phase displacement is 60
minutes. The limit of the composite error at the rated accuracy limit primary current
is 5 percent.
The approximate value of the accuracy limit factor F
a
corresponding to the actual
current transformer burden can be calculated on the basis of the rated accuracy
limit factor F
n
at the rated burden, the rated burden S
n
, the internal burden S
in
and
the actual burden S
a
of the current transformer.
F
F
S
S
S
S
a
n
in
n
in
a
=
×
+
+
(Equation 420)
F
a
The approximate value of the accuracy limit factor ( ALF) corresponding to the
actual CT burden
F
n
The rated accuracy limit factor at the rated burden of the current transformer
S
n
The rated burden of the current transformer
S
in
The internal burden of the current transformer
S
a
The actual burden of the current transformer
Class X defines the CT knee-point voltage U
kn
as a sinusoidal voltage applied to
the CT secondary (primary open) which, when increased by 10 %, causes the CT
magnetizing current to increase by 50 %. The relationship between the actual
accuracy limit factor F
a
and the CT knee-point voltage, assuming resistive burden,
is U
kn
= k * F
a
* I
n
* (R
in
+ R
a
) where I
n
= CT rated secondary current, R
in
= CT
internal resistance and R
a
= CT's actual burden in ohms. Factor k depends on the CT
magnetizing curve. The value k = 1.0 is used in IEC 61869-2:2012.
Requirements for measurement
transformers
1MRS759142 F
1918
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......