J01
Feeder #1 panel
J02
Feeder #2 panel
Q0
Circuit breaker (CB)
TO1
Relay trip output #1
TO2 Relay trip output #2
A1
Protection relay
TC1
CB trip coil 1
TC2
CB trip coil 2
F1
Miniature circuit breaker
In example 2, the fail-safe approach aims at securing circuit breaker tripping even
if a relay fails. A relay in a panel measures also the adjacent panel’s currents (and
voltages) and receives the necessary primary device’s position information. In other
words, the relay in a panel functions as a backup relay for the adjacent panel.
This approach allows service continuation while the failed relay is waiting for spare
parts or a complete replacement. The backup protection features provided by the
adjacent panel’s relay do not necessarily fully match the features available in the
main relay.
TC1
TC2
C
Control -
-A2
-A1
TO
-F1
-Q0
TO
AUX. POWER
AUX. POWER
Figure 37: Redundant protection fail-safe principle, example 3
Q0
Circuit breaker (CB)
A1
Protection relay #1
A2
Protection relay #2
TO
Protection relay trip output
TC1
CB trip coil 1
TC2
CB trip coil 2
F1
Miniature circuit breaker
In example 3, the fail-safe approach aims at securing circuit breaker tripping even if
one of the redundant relays fails. The scheme is often referred to as the 1-outof- 2
approach. This approach allows service continuation while the failed relay is waiting
for spare parts or a complete replacement. The redundancy in this example covers
relays and circuit breaker tripping coils but it can be expanded to auxiliary power
supplies (two station batteries and isolated distribution), cabling, circuit breaker
failure protection, and so on. Another variant of this approach is to have a main relay
and a backup relay instead of two fully redundant relays. The backup relay does not
1MRS759142 F
Basic functions
REX640
Technical Manual
115
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......