non-directional distance zone or overcurrent stage, is required for fault indication.
The
START
and
START_DLYD
inputs are available for the purpose.
• The
START
input has no delay. Thus, a switch-onto-fault situation is immediately
signalled to SOTF control.
•
START_DLYD
is used when an additional delay is required to start the signal. The
switch-onto-fault situation is signalled to the SOTF control after the set
Operate
delay time.
Dead-line detector
The dead line detection should be used only when the voltage
transformers are located on the line side of the circuit breaker.
The
Automatic SOTF Ini setting is used to configure the internal dead line detection
function.
Table 1167: Options for dead line detection
Automatic SOTF Ini
Description
DLD disabled
The dead line detection function is disabled. This operation
mode must be applied when voltage transformers are loca-
ted on the bus side of the circuit breaker.
Voltage
The dead line detection function is enabled and based sole-
ly on the undervoltage condition. A dead line condition is
declared, if all the phase voltages are below the
Voltage dead
Lin Val
setting. The dead line is detected if the dead line
condition is declared and simultaneously no fault is detected
by the
START
and
START_DLYD
inputs . The dead line con-
dition is signalled to the SOTF control after the delay defined
with the
Dead line time
setting.
Current
The dead line detection function is enabled and based sole-
ly on the undercurrent condition. A dead line condition is
declared, if all the phase currents are below the
Current dead
Lin Val
setting. The dead line is detected if the dead line
condition is declared and simultaneously no fault is detected
by the
START
and
START_DLYD
inputs. The dead line condi-
tion is signalled to the SOTF control after delay defined with
the
Dead line time
setting.
Current & Voltage
The dead line detection function is enabled and based on un-
dercurrent and undervoltage condition. A dead line condition
is declared, if all the phase currents are below the
Current
dead Lin Val
setting and simultaneously all phase voltages
are below the
Voltage dead Lin Val
setting. The dead line is
detected if the dead line condition is declared and simulta-
neously no fault is detected by the
START
and
START_DLYD
inputs. The dead line condition is signalled to the SOTF con-
trol after delay defined with the
Dead line time
setting.
SOTF detection
The purpose of this module is to detect the switch onto fault situation based on
the current and voltage measurements. If the voltage, in any of the phases, is below
the
Voltage dead Lin Val setting and simultaneously the current in the same phase
1MRS759142 F
Protection related functions
REX640
Technical Manual
1225
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......