Connecting of test equipment to the protection relay
Before testing, connect the test equipment according to the protection relay
specific connection diagram.
Pay attention to the correct connection of the input and output current terminals.
Check that the input and output logical signals in the logic diagram for the function
under test are connected to the corresponding binary inputs and outputs of the
protection relay. Select the correct auxiliary voltage source according to the power
supply module of the protection relay. Select the correct auxiliary voltage source
according to the power supply module of the protection relay.
A
IM1001
.X
2
1
2
3
4
5
6
REX640
Breakable
terminal blocks
Test device
1
2
5
7
6
TIMER
STOP
A
P1
P2
S1
S2
8
PSM100x
.X
1
PSM100x
.X
2
Figure 377: Example of connections to test the line differential protection relay
Secondary current injection
There are two alternative modes to check the operation of a line differential
protection relay. These are not exclusive methods for each other and can be used for
various test on the protection relay.
Normal mode
In normal mode, that is, the mode when the function is on normal operation, the
local end protection relay sends phasors to the remote end protection relay and
receives phasors measured by the remote end protection relay. This mode can be
Protection functions
1MRS759142 F
668
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......