Transformer overcurrent protection
The purpose of transformer overcurrent protection is to operate as main protection,
when differential protection is not used. It can also be used as coarse back-up
protection for differential protection in faults inside the zone of protection, that
is, faults occurring in incoming or outgoing feeders, in the region of transformer
terminals and tank cover. This means that the magnitude range of the fault current
can be very wide. The range varies from 6xI
n
to several hundred times I
n
, depending
on the impedance of the transformer and the source impedance of the feeding
network. From this point of view, it is clear that the operation must be both very
fast and selective, which is usually achieved by using coarse current settings.
The purpose is also to protect the transformer from short circuits occurring outside
the protection zone, that is through-faults. Transformer overcurrent protection also
provides protection for the LV-side busbars. In this case the magnitude of the fault
current is typically lower than 12xI
n
depending on the fault location and transformer
impedance. Consequently, the protection must operate as fast as possible taking
into account the selectivity requirements, switching-in currents, and the thermal
and mechanical withstand of the transformer and outgoing feeders.
Traditionally, overcurrent protection of the transformer has been arranged as
shown in
. The low-set stage PHLPTOC operates time-selectively both
in transformer and LV-side busbar faults. The high-set stage PHHPTOC operates
instantaneously making use of current selectivity only in transformer HV-side
faults. If there is a possibility, that the fault current can also be fed from the
LV-side up to the HV-side, the transformer must also be equipped with LV-side
overcurrent protection. Inrush current detectors are used in start-up situations to
multiply the current start value setting in each particular protection relay where the
inrush current can occur. The overcurrent and contact based circuit breaker failure
protection CCBRBRF is used to confirm the protection scheme in case of circuit
breaker malfunction.
Figure 200: Example of traditional time selective transformer overcurrent protection
Protection functions
1MRS759142 F
332
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......