6.4.5
Application
Communication principle
Analog samples, trip-, start- and user programmable signals are transferred in each
protection telegram and the exchange of these protection telegrams is done eight
times per power system cycle (every 2.5 ms when F
n
= 50 Hz).
Master-Master communication arrangement is used in the two-terminal line
differential solution. Current samples are sent from both line ends and the
protection algorithms are also executed on both line ends. The direct-intertrip,
however, ensures that both ends are always operated simultaneously.
Time synchronization
In numerical line differential protection, the current samples from the protections
which are located geographically apart from each other must be time coordinated
so that the current samples from both ends of the protected line can be compared
without introducing irrelevant errors. The time coordination requires an extremely
high accuracy.
As an example, an inaccuracy of 0.1 ms in a 50 Hz system gives a maximum
amplitude error of approximately around 3 percent. An inaccuracy of 1 ms gives
a maximum amplitude error of approximately 31 percent. The corresponding figures
for a 60 Hz system are 4 and 38 percent respectively.
In the protection relay, the time coordination is done with an echo method. The
protection relays create their own time reference between each other so that the
system clocks do not need to synchronize.
The figure shows that in the time synchronization the transmission time to send
a message from station B to station A, T1→T2, and the time to receive a message
from A to B, T4→T5, are measured. The station A protection relay delay from the
sampling to the start of send, T3→T4, and the local delay from receive to the
station B protection relay sampling T5→T6 time, are also measured for the station B
protection relay, and vice versa. This way the time alignment factor for the local and
remote samples is achieved.
Figure 756: Measuring sampling latency
P
T
T
T
T
d
=
−
+
−
(
)
(
)
2
1
5
4
2
(Equation 317)
S
P
T
T
T
T
d
d
=
+
−
+
−
(
)
(
)
4
3
6
5
(Equation 318)
1MRS759142 F
Supervision functions
REX640
Technical Manual
1329
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......