The function contains a blocking functionality. It is possible to block function
outputs, timers or the function itself.
4.1.1.4
Analog input configuration
PHxPTOC has one analog group input which must be properly configured.
Table 362: Analog inputs
Input
Description
I3P
Three-phase currents
See the preprocessing function blocks in this document for the possible
signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.1.1.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of PHxPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
OPERATE
Level
detector
Phase
selection
logic
BLOCK
START
ENA_MULT
t
Timer
t
I3P
I_A
I_B
I_C
Blocking
logic
Figure 198: Functional module diagram
Level detector
The measured phase currents are compared phasewise to the set
Start value. If the
measured value exceeds the set
Start value, the level detector reports the exceeding
of the value to the phase selection logic. If the
ENA_MULT
input is active, the
Start
value setting is multiplied by the Start value Mult setting.
The protection relay does not accept the
Start value or Start value Mult
setting if the product of these settings exceeds the
Start value setting
range.
1MRS759142 F
Protection functions
REX640
Technical Manual
327
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......