exceeds the
Current dead Lin Val setting, the SOTF situation is signalled to SOTF
control module after the set
Cur voltage Det time.
SOTF control
The SOTF control module needs to be activated before the operation is possible
in the switch-onto-fault situation. There are two ways to activate the SOTF control
module.
• By CB_CL_CMD (circuit breaker closing command).
• By the dead line condition received from the dead line detection module.
Dead line detection should be used only when the voltage transformers
are located on the line side of the circuit breaker.
When the
CB_CL_CMD
input is activated or the dead line condition is detected, the
SOTF control module becomes active. The reset timer is started when
CB_CL_CMD
is inactivated or the dead line condition disappears. Thus, the module becomes
inactive after the set
SOTF reset time is exceeded.
When the SOTF control module is active, the
Operation mode setting defines the
operation criteria for the detection of a switch-onto-fault condition. The detection
can be based on the external start signals from the distance or overcurrent
functions, on the measured internal voltage and current levels, or on both.
Table 1168: Options for SOTF detection
Operation mode
Description
Start
The
OPERATE
output is activated immediately after a signal
from the trigger module. This indicates that the breaker is
closed onto fault.
Current & Voltage
The
OPERATE
output is activated immediately after a signal
from the SOTF detection module. This indicates that the
breaker is closed onto fault. This operation mode can be
used, for example, if the non-directional distance zone is not
available.
Both
The
OPERATE
output is activated immediately after a signal
from the trigger or SOTF detection modules. This indicates
that the breaker is closed onto fault.
The
OPERATE
output can be blocked by activating the
BLOCK
input.
5.8.6
Application
The operation of CVPSOF is generally based on the non-directional distance zone or
the non-directional overcurrent stage. When the feeder-side voltage transformers
are used for providing the polarization quantity for the distance or directional
overcurrent protection, the use of non-directional impedance or current based
protection for starting CVPSOF secures a fast switch-onto-fault tripping in the
close-in three-phase short circuits. The non-directional protection provides a fast
fault clearance when the protection is used for energizing a bus from the feeder
with a short circuit fault in it. Other protection functions, like time delayed zero-
sequence overcurrent functions, can be connected to CVPSOF to increase the
dependability of the scheme. The other main advantage of using CVPSOF is that it
Protection related functions
1MRS759142 F
1226
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......