The operation of PREVPTOC can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
OPERATE
Level
detector
BLOCK
START
I3P
I
2
t
Timer
Figure 475: Functional module diagram
Level detector
The level detector compares the negative-sequence current to the set
Start value. If
the I
2
value exceeds the set
Start value, the level detector sends an enabling signal
to the timer module.
Timer
Once activated, the timer activates the
START
output. When the operation timer
has reached the set
Operate delay time value, the
OPERATE
output is activated. If
the fault disappears before the module operates, the reset timer is activated. If the
reset timer reaches the value of 200 ms, the operation timer resets and the
START
output is deactivated.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is
available in the monitored data view.
4.4.4.6
Application
The rotation of a motor in the reverse direction is not a desirable operating
condition. When the motor drives fans and pumps, for example, and the rotation
direction is reversed due to a wrong phase sequence, the driven process can be
disturbed and the flow of the cooling air of the motor can become reversed too.
With a motor designed only for a particular rotation direction, the reversed rotation
direction can lead to an inefficient cooling of the motor due to the fan design.
In a motor, the value of the negative-sequence component of the phase currents is
very negligible when compared to the positive-sequence component of the current
during a healthy operating condition of the motor. But when the motor is started
with the phase connections in the reverse order, the magnitude of I
2
is very high.
So whenever the value of I
2
exceeds the start value, the function detects the reverse
rotation direction and provides an operating signal that disconnects the motor
from the supply.
4.4.4.7
Signals
1MRS759142 F
Protection functions
REX640
Technical Manual
839
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......