COIL_STS
COIL_POS
CL_RESISTOR
OP_RESISTOR
Level detector
U3P
Network
parameters
calculation
Coil automatic
tuning
Resistor
control
Coil manual
tuning
URES
FIXCOIL_STS
RESISTOR_STS
HIGH_LIMIT
LOW_LIMIT
ST_CALIB
IRES
ST_TUNING
BLK_MANUAL
BLK_AUTO
ST_RESIS_SEQ
RAISE_LOCAL
LOWER_LOCAL
BLK_RESISTOR
ALARM
EARTH_FAULT
TUNING_ACT
RAISE_OWN
LOWER_OWN
FIXCOIL
OP_FIXCOIL
RESISTOR
Coil
commissioning
CL_FIXCOIL
Measurement
selection
MOT_ALARM
POT_ALARM
TUNING_SUC
Figure 923: Functional module diagram
9.11.6.1
Measurement selection
PASANCR supports two possibilities for zero-sequence voltage and coil position
measurement.
Voltage measurement setting is used to define the location of voltage
measurement: from busbar or from coil. Busbar measurement is usually an open-
delta connection of phase-to-earth voltage transformers. Coil measurement is
available from the arc suppression coil's measurement winding.
Position Meas mode setting is used to select the measurement between coil
position indication and coil position indication with a CT or sensor. "Pos. indication"
option uses the potentiometer-based
COIL_POS
information only. If "Pos. ind. and
meas." option is selected, the measured
IRES
is used for the control algorithm. In
this case, the
COIL_POS
signal works as a backup and is switched automatically into
use if the coil is disconnected from the network.
9.11.6.2
Level detector
Level detector op setting is used to enable or disable the Level detector module.
"Enable" means that the Level detector module is enabled and can be used to start
the tuning procedure.
When "Disable" is selected, the automatic coil tuning procedure can be
started with input
ST_TUNING
.
Control functions
1MRS759142 F
1734
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......