
Voltage start value
Maximum
healthy-state
Uo
Margin
Resonance Curve
of
few %
Uo [%]
lcoil: A
20
68 A
40
60
80
100
120
Figure 320: Example of selection of setting Voltage start value to maximize the
earth-fault detection sensitivity based on the resonance curve calculated by the coil
controller
There are three MFADPSDE instances (stages) available. The sensitivity
of different stages should be selected differently. For example, stage
1 could have the highest
Voltage start value and the shortest Operate
delay time. Thus it would fulfill the requirements for protection operation
speed by providing fast operation for low-ohmic earth faults. Stage 2
should have lower
Voltage start value and longer Operate delay time
compared with stage 1. This stage would fulfill the requirements for
protection sensitivity (in terms of fault resistance value). Stage 3 could
be used to detect high-ohmic earth faults and generate alarms for them.
To maximize the earth-fault detection sensitivity of stage 3,
Voltage start
value should be selected based on the network's resonance curve (see
Such coordination of different protection stages enables:
• Indication (but no tripping) of transient, self-extinguishing earth faults, where
the zero-sequence voltage may temporarily rise to a high value and then decay
slowly away. This can be achieved by monitoring the
START
outputs. Delayed
operation times of stages 1 and 2 avoid unnecessary breaker operations during
self-extinguishing earth faults.
• Fast tripping of low-ohmic permanent earth faults regardless of their type
(continuous or intermittent), stage 1
• Delayed tripping of higher-ohmic permanent earth faults regardless of their type
(continuous or intermittent), stage 2
1MRS759142 F
Protection functions
REX640
Technical Manual
557
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......