
Figure 410: Operation logic of the biased low stage
The high currents passing through a protected object can be caused by the short
circuits outside the protected area, the high currents fed by the transformer in
a motor startup or transformer inrush situations. Therefore, the operation of
the differential protection is biased with respect to the load current. In biased
differential protection, the higher the differential current required for the protection
to trip, the higher the load current.
The operation characteristic of the biased low stage is determined by
Low operate
value, Slope section 2 and the second turning point setting of the operating
characteristic curve,
End section 2 (the first turning point and the slope of the last
part of the characteristic are fixed). The settings are the same for each phase. When
the differential current exceeds the operating value determined by the operating
characteristic, the differential function is activated. If the differential current stays
above the operating value continuously for a suitable period, the
OPR_LS
output is
activated. The activation of the
OPR_LS
output activates the OPERATE output.
The stage can be blocked internally by the second or the fifth harmonic restraint,
or by special algorithms detecting the inrush and current transformer saturation at
external faults. When the operation of the biased low stage is blocked by the second
harmonic blocking functionality, the
BLKD2H
output is activated.
The
BLKD5H
output is activated when the biased low stage is blocked by the fifth
harmonic blocking functionality. Correspondingly, when the operation of the biased
1MRS759142 F
Protection functions
REX640
Technical Manual
725
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......