by a binary input, a horizontal communication input or an internal signal of the
protection relay's program. The influence of the
BLOCK
input signal activation is
preselected with the global
Blocking mode setting.
The
Blocking mode setting has three blocking methods. In the "Freeze timers"
mode, the operation timer is frozen to the prevailing value, but the
OPERATE
output
is not deactivated when blocking is activated. In the "Block all" mode, the whole
function is blocked and the Timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the
OPERATE
output is not activated.
The “Freeze timers” mode of blocking has no effect during the “Inverse
reset” mode.
4.5.2.6
Timer characteristics
The operating curve types supported by PHPTUV are:
Table 793: Supported IDMT operate curve types
Operating curve type
(5) ANSI Def. Time
(15) IEC Def. Time
(21) Inv. Curve A
(22) Inv. Curve B
(23) Programmable
4.5.2.7
Application
PHPTUV is applied to power system elements, such as generators, transformers,
motors and power lines, to detect low voltage conditions. Low voltage conditions
are caused by abnormal operation or a fault in the power system. PHPTUV can
be used in combination with overcurrent protections. Other applications are the
detection of a no-voltage condition, for example before the energization of a high
voltage line, or an automatic breaker trip in case of a blackout. PHPTUV is also used
to initiate voltage correction measures, such as insertion of shunt capacitor banks,
to compensate for a reactive load and thereby to increase the voltage.
PHPTUV can be used to disconnect from the network devices, such as electric
motors, which are damaged when subjected to service under low voltage
conditions. PHPTUV deals with low voltage conditions at power system frequency.
Low voltage conditions can be caused by:
• Malfunctioning of a voltage regulator or incorrect settings under manual control
(symmetrical voltage decrease)
• Overload (symmetrical voltage decrease)
• Short circuits, often as phase-to-earth faults (unsymmetrical voltage increase).
PHPTUV prevents sensitive equipment from running under conditions that could
cause overheating and thus shorten their life time expectancy. In many cases,
PHPTUV is a useful function in circuits for local or remote automation processes
in the power system.
1MRS759142 F
Protection functions
REX640
Technical Manual
863
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......