
Faulted phase information is not given in case of cross-country fault
(
XC_FLT = TRUE
).
Fault resistance estimation
Protection function IFPTOC includes fault resistance (R
F
) magnitude estimation
based on information on the faulted phase, the faulted phase voltage and estimated
earth fault current magnitude (fundamental frequency). Fault resistance magnitude
can be estimated with equation:
(Equation 141)
Where
= Faulted phase voltage magnitude, fundamental frequency [V]
= Estimated earth-fault current magnitude, fundamental frequency [A]
Actual implementation utilizes Cumulative Phasor Summing (CPS).
Magnitude of estimated fault resistance in primary ohms is available in
Recorded data:
Fault resistance. In monitored data this information is
given: RF.
Fault resistance estimation is not done in case of cross-country fault
(
XC_FLT = TRUE
).
In case of intermittent earth fault, fault resistance estimation is not
accurate.
Trip logic
Protection function IFPTOC supports both tripping and alarming earth-fault
handling defined with setting
Operation mode = “Alarming EF” or “Tripping EF”.
With
Operation mode = “Alarming EF”,
OPERATE
and corresponding
OP_EF/OP_XC/
OP_SOTF/OP_INTR
outputs are not activated.
Operation mode = “Alarming EF” is
applicable in networks, where due to low touch voltages tripping of earth-fault
is not required (requires existence of Global Earthing System, GES). Monitoring
of prevailing earth-fault current and/or touch voltage magnitude can be done via
Monitored data.
When start conditions of touch voltage protection, earth-fault current protection,
cross-country fault protection, intermittent earth-fault protection or switch
onto fault protection are fulfilled, this is indicated by activation of
START
and corresponding
ST_EF/ST_XC/ST_SOTF/ST_INTR
outputs. When operate
conditions are fulfilled and setting
Operation mode = “Tripping EF”, this is indicated
by activation of
OPERATE
and corresponding
OP_EF/OP_XC/OP_SOTF/OP_INTR
outputs.
1MRS759142 F
Protection functions
REX640
Technical Manual
635
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......