Characteristic
Value
Reset ratio
Typically 1.04
Retardation time
Total retardation time when the impedance
returns from the operating circle <40 ms
Operate time accuracy
±1.0% of the set value or ±20 ms
Suppression of harmonics
-50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
4.7.3.11
Technical revision history
Table 957: UEXPDIS Technical revision history
Product
connectivi
ty level
Technical
revision
Change
PCL4
C
Added support for settable blinder in offset mho characteristic.
4.7.4
Three-phase underimpedance protection UZPDIS (ANSI
21G)
4.7.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase underimpedance pro-
tection
UZPDIS
Z<G
21G
4.7.4.2
Function block
Figure 569: Function block
4.7.4.3
Functionality
The three-phase underimpedance protection UZPDIS is generally applied as a
backup protection for generators and transformers against short circuit faults.
The protection is based on the origin-centric circular characteristics on the
impedance plane. The function calculates the impedance value from the voltage
and current phasors. If the impedance vector enters the origin-centric circle, the
function produces the operating signal after a set delay. The operating time
characteristics are according to definite time (DT).
However, it is also possible to enable separate zones of offset-mho based
protection with multiple instances of the function.
Protection functions
1MRS759142 F
1026
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......