from origin to include some margin for the admittance operation point due to
CT/VT-errors, when fault is located outside the feeder.
Conductance forward: 15 A/(15 kV/sqrt(3)) * 0.2 = +0.35 mS corresponding to 3.0
A (at 15 kV). The selected value provides margin considering also the effect of
CT/VT-errors in case of outside faults.
In case of a lower rated value of the parallel resistor, for example, 5 A (at 15 kV), the
recommended security margin should be higher, for example 0.7, so that sufficient
margin for CT/VT-errors can be achieved.
Susceptance forward
By default, this setting should be based on the minimum operate current of 1 A.
Susceptance forward: 1 A/(15 kV/sqrt(3)) = +0.1 mS
Susceptance reverse
This setting should be set based on the value of the maximum earth-fault current
produced by the feeder (considering possible feeder topology changes) with a
security margin. This ensures that the admittance operating point stays inside
the "Box"-characteristics during outside fault. The recommended security margin
should not be lower than 1.5.
Susceptance reverse: - (10 A * 1.5)/ (15 kV/sqrt(3)) = -1.73 mS
Conductance reverse
This setting is used to complete the non-directional characteristics by closing the
"Box"-characteristic. In order to keep the shape of the characteristic reasonable and
to allow sufficient margin for the admittance operating point during outside fault, it
is recommended to use the same value as for setting Susceptance reverse.
Conductance reverse = -1.73 mS
Figure 295: Admittances of the example
4.2.4.8
Signals
Protection functions
1MRS759142 F
512
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......