When the reactive power exceeds
Min reactive power and flows in the operating
area, the module sends an enable signal to the Timer indicating that the reactive
power is being consumed at the grid connection point. A slight tilt in the curve can
be obtained by the setting
Pwr sector reduction.
To avoid false tripping, reactive power calculation is blocked if the magnitude of
positive sequence current is less than the set
Min Ps Seq current.
The magnitude of calculated reactive power Q is available in the Monitored data
view.
Figure 600: Operating area of DQPTUV function
Quadrant II Generator produces active power, but draws reactive power (under-excited)
Quadrant III Generator produces both active and reactive power
The power direction can be reversed by setting
Pol reversal to “True”.
Timer
Once activated by both Under voltage detection and Reactive power monitoring
module, the Timer activates the
START
output. The Timer characteristic is according
to DT. When the operation timer has reached the value set by
Operate delay
time, the
OPERATE
output is activated. If the fault disappears before the module
operates, the Timer is reset instantaneously.
The Timer calculates the start duration value "START_DUR" which indicates the
percentage ratio of the start situation and the set operating time. The value is
available through the Monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the
BLOCK
input and the global setting Configuration > System >
Blocking mode which selects the blocking mode. The
BLOCK
input can be controlled
Protection functions
1MRS759142 F
1074
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......