Weak-end infeed (WEI) logic
Do not use the WEI function at both feeder ends. It can only be enabled
at the weak end.
The WEI logic is recommended to be used only in the permissive schemes.
Setting guidelines for current reversal logic
Reversal reset time: This setting can be set to the maximum reset time of the
communication channel. A minimum setting of 40 ms is recommended. A long
Reversal reset time setting increases the security against unwanted tripping, but
delays the fault clearing if the fault develops from one feeder to involve the other.
However, the probability of this type of fault is small.
Reversal time: Set the start delay reversal time below 80 percent of the breaker
operate time, but to a minimum of 20 ms.
Setting guidelines for Weak-end infeed (WEI) logic
The WEI logic returns the received carrier signal with the
ECHO
output when it
receives the carrier signal (CR) if no fault has been detected by the forward and
reverse directional measuring elements and the duration is longer than the
Wei Crd
time coordination time delay setting. To prevent the spurious carrier receive signals
from activating the WEI logic and causing unwanted communication, the
Wei Crd
time setting can be set to "0.010 s".
5.13.7
Signals
5.13.7.1
RCRWPSCH Input signals
Table 1206: RCRWPSCH Input signals
Name
Type
Default
Description
URES
SIGNAL
-
Residual voltage
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
BLK_IRV
BOOLEAN
0=False
Block of current rever-
sal function
BLK_WEI1
BOOLEAN
0=False
Block of WEI Logic
BLK_WEI2
BOOLEAN
0=False
Block of WEI logic due
to operation of other
protections
IRV
BOOLEAN
0=False
Activation of current
reversal logic
FF
BOOLEAN
0=False
Block of trip from
WEI logic through
fuse-failure function
Table continues on the next page
1MRS759142 F
Protection related functions
REX640
Technical Manual
1279
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......