
The
START
output is activated once
Start delay time has elapsed.
OPERATE
output
is activated once
Operate delay time has elapsed and the above three conditions
are valid. Reset timer is started if any of the above three conditions is not
valid. If the fault is transient and self-extinguishes,
START
output stays activated
until the elapse of reset timer (setting Reset delay time). After
OPERATE
output
activation,
START
and
OPERATE
outputs are reset immediately, if any of the above
three conditions is not valid. The start duration value START_DUR, available in the
Monitored data view, indicates the percentage ratio of the start situation and the
set operating time.
If detection of temporary earth faults is not desired, the activation of
START
output can be delayed with setting
Start delay time. The same
setting can also be used to avoid restarting of the function during long
lasting post-fault oscillations, if time constant of post-fault oscillations is
very long (network losses and damping is low).
To keep the operate timer activated between current spikes during
intermittent or restriking earth fault, the
Reset delay time should be set
to a value exceeding the maximum expected time interval between fault
spikes (obtained at full resonance condition). Recommended value is at
least 300 ms.
Protection functions
1MRS759142 F
570
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......