Figure 896: Signal scheme of autoreclosing operation initiated with protection start
signal
The autoreclosing shot is initiated with a start signal of the protection function
after the start delay time has elapsed. The autoreclosing starts when the
Str 2 delay
shot 1 setting elapses.
Figure 897: Signal scheme of autoreclosing operation initiated with protection
operate signal
The autoreclosing shot is initiated with a trip signal of the protection function. The
autoreclosing starts when the protection operate delay time elapses.
Normally, all trip and start signals are used to initiate an autoreclosing shot and
trip the circuit breaker.
ACTIVE
output indicates reclosing sequence in progress.
If any of the input signals
INIT_X
or
DEL_INIT_X
are used for blocking, the
corresponding bit in the
Tripping line setting must be FALSE. This is to ensure
that the circuit breaker does not trip from that signal, that is, the signal does not
activate the
OPEN_CB
output. The default value for the setting is "63", which means
that all initiation signals activate the
OPEN_CB
output. The lowest bit in the
Tripping
line setting corresponds to the
INIT_1
input, the highest bit to the
INIT_6
line.
Control functions
1MRS759142 F
1668
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......