POSCLOSE
I >
From Level detector 1
Timer 1 elapsed
From Timer 1
OR
AND
AND
CB fail retrip mode
”Without check”
CB fail retrip mode
”Current check”
CB failure mode ”Current”
CB failure mode ”Breaker
status”
CB failure mode ”Both(OR)”
AND
AND
AND
OR
OR
AND
TRRET
BLOCK
CB_FAULT_AL
From Timer 3
AND
AND
CB failure mode ”Both(AND)”
Figure 663: Retrip logic
Backup trip logic
Timer 2 activates Backup trip logic, which gives a backup trip
TRBU
for the upstream
circuit breaker if the main circuit breaker fails to clear the fault. Backup trip logic is
also activated if the timer-enabling signal from the Start logic module (rising edge
of the
START
input detected) and
CB_FAULT_AL
are both active.
The operation of Backup trip logic depends on the settings
CB failure mode and CB
failure trip mode as shown in
Table 1115: Backup trip logic operation
Value of setting CB
failure mode
Value of setting CB
failure trip mode
Conditions for activating Backup trip logic
Current
1 out of 3
Any phase current exceeds
Current value
set-
ting.
1 out of 4
Either of the following is true:
• Any phase current exceeds
Current value
setting.
• The residual current exceeds
Current val-
ue Res
setting.
2 out of 4
Either of the following is true:
• Any phase current exceeds
Current value
setting and the residual current exceeds
Current value Res
setting.
Table continues on the next page
1MRS759142 F
Protection related functions
REX640
Technical Manual
1169
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......