Name
Type
Description
GRPOFF
Group signal
Group off signal for function blocks
DEV_WARN
BOOLEAN
Protection relay internal warning
FRQ_ADP_WARN
BOOLEAN
Frequency adaptivity warning
FRQ_ADP_FAIL
BOOLEAN
Frequency adaptivity status fail
FRQ_ADP_BU
BOOLEAN
Main frequency adaptivity source
3.7.4
Settings
Table 69: PROTECTION Settings
Parameter
Values (Range)
Unit
Step
Default
Description
SG operation mode
1=Operator
2=Logic mode 1
3=Logic mode 2
1=Operator
Operation mode for setting
group change
3.8
Local/Remote control CONTROL
3.8.1
Function block
Figure 50: Function block
3.8.2
Functionality
Local/Remote control is by default realized through the R/L button on the front
panel. The control via binary input can be enabled by setting the value of the
LR control setting to "Binary input". The binary input control requires that the
CONTROL function is instantiated in the product configuration.
Local/Remote control supports multilevel access for control operations in
substations according to the IEC 61850 standard. Multilevel control access with
separate station control access level is not supported by other protocols than IEC
61850.
The actual Local/Remote control state is evaluated by the priority scheme on the
function block inputs. If more than one input is active, the input with the highest
priority is selected. The priority order is “off”, “local”, “station”, “remote”, “all”.
1MRS759142 F
Basic functions
REX640
Technical Manual
135
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......