This conflict status is available in the monitored data CONFL_STATUS as given in
Table 1548: States of CONFL_STATUS
Monitored data
Value
CONFL_STATUS
1 (“No conflict”)
2 (“Multiple NSCB sync”)
3 (“Multiple SCB sync”)
4 (“NSCB and SCB sync”)
Source selection logic
Source selection logic is responsible for the selection and coordination of the
sources for the voltage and frequency matching. It is enabled only when the
autosynchronization function of the selected NSCB is in “Semiautomatic” or
“Automatic” mode.
A source is available for participation in the voltage and frequency matching if the
corresponding autosynchronization function is in “Semi-automatic” or “Automatic”
mode and the host protection relay is in remote mode. This information is received
from the corresponding source via input signals
SRC1_ASC_DAT
...
SRC8_ASC_DAT
.
All the sources in the network can be divided into nine participation groups based
on topology and their availability for participation.
Table 1549: Groups for source participation (monitored data
SRC1_PTC_GRP...SRC8_PTC_GRP)
Source participation group
Description
Group 1
All the sources which are unavailable for participation, are
electrically connected to the grid or are not part of either
subnetwork which must be synchronized by the selected CB.
Group 2
The sources which do not belong to Group 1 and are part of
the subnetwork which includes the lower-number busbar of
the two busbars connected across the selected CB.
Group 3
The sources which do not belong to Group 1 and are part
of the other subnetwork, which includes the higher-number
busbar.
Group 4
The sources in Group 2 which are not ready for participation
in matching.
Group 5
The sources which are part of Group 3, but not ready for
participation in matching.
Group 6
The sources which are part of Group 2 or Group 3, but the
network is internally connected and setting
Synchrocheck
mode
in ASNSCSYN is "Synchronous"
Group 7
The sources which are part of Group 2 or Group 3, but
the network is internally connected and the setting
Synchro-
check mode
in ASNSCSYN is "Asynchronous".
Group 8
The sources which are part of Group 2 or Group 3, but the
network is internally asynchronous and setting
Synchrocheck
mode
in ASNSCSYN is "Synchronous".
Group 9
The sources which are part of Group 2 or Group 3, but setting
Synchrocheck mode
in ASNSCSYN is "Off".
Control functions
1MRS759142 F
1616
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......