Level detector 1
The calculated compensated unbalance current I_AMPL_COMP is compared to the
set "Start value". If I_AMPL_COMP exceeds the set "Start value", the Level detector 1
sends an enabling signal to the Timer 1 module.
Timer 1
Once activated, the Timer 1 module activates the
START
output. Depending on the
value of the
Operating curve type setting, the time characteristics are according
to DT or IDMT. When the operation timer has reached the value of
Operate delay
time in the DT mode or the maximum value defined by the inverse time curve, the
OPERATE
output is activated. When the user-programmable IDMT curve is selected,
the operation time characteristics are defined by the parameters
Curve parameter
A, Curve parameter B, Curve parameter C and Curve parameter E.
In a drop-off situation, that is when a fault suddenly disappears before the operate
delay is exceeded, the Timer 1 reset state is activated. The functionality of the Timer
1 in the reset state depends on the combination of the Operating curve type and
Reset delay time settings. When the DT characteristic is selected, the reset timer
runs until the set
Reset delay time value is exceeded. When the IDMT curves are
selected, an immediate reset occurs. The
START
output is deactivated when the
reset timer has elapsed.
The setting
Time multiplier is used for scaling the IDMT operation and reset times.
The setting parameter
Minimum operate time defines the minimum desired
operation time for IDMT. The setting is applicable only when the IDMT curves are
used.
The
Minimum operate time setting should be used with great care
because the operation time is according to the IDMT curve but always
at least the value of the
Minimum operate time setting.
The Timer 1 module calculates the start duration value START_DUR, which indicates
the percentile ratio of the start situation and the set operation time. The value is
available in the monitored data view.
In a typical double-Y-connected configuration (
), there are two branches
in every phase and hence six individual counters COUNT_BR1_A, COUNT_BR2_A,
COUNT_BR1_B, COUNT_BR2_B, COUNT_BR1_C and COUNT_BR2_C are maintained.
Based on the phase angle of the compensated unbalance current I_ANGL_COMP,
the phase and the branch of the element failure location is detected. However,
the element failure location also depends on the type of capacitor banks, that is,
whether internal or external fuses are used. The setting
Fuse location is used to set
the capacitor bank type as “External” or “Internal”.
For an external fuse capacitor bank, the element failure location and corresponding
counters to be incremented are determined based on the phase angle of the
compensated unbalance current.
1MRS759142 F
Protection functions
REX640
Technical Manual
1123
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......