Table 505: Reset time characteristics supported by different stages
Reset curve type
EFLPTOC
EFHPTOC
Note
(1) Immediate
x
x
Available for all operate time curves
(2) Def time reset
x
x
Available for all operate time curves
(3) Inverse reset
x
x
Available only for ANSI and user pro-
grammable curves
The
Type of reset curve setting does not apply to EFIPTOC or when the
DT operation is selected. The reset is purely defined by the
Reset delay
time setting.
4.2.1.8
Application
EFxPTOC is designed for protection and clearance of earth faults in distribution
and sub-transmission networks where the neutral point is isolated or earthed
via a resonance coil or through low resistance. It also applies to solidly earthed
networks and earth-fault protection of different equipment connected to the power
systems, such as shunt capacitor bank or shunt reactors and for backup earth-fault
protection of power transformers.
Many applications require several steps using different current start levels and time
delays. EFxPTOC consists of three different protection stages.
• Low EFLPTOC
• High EFHPTOC
• Instantaneous EFIPTOC
EFLPTOC contains several types of time-delay characteristics. EFHPTOC and
EFIPTOC are used for fast clearance of serious earth faults.
4.2.1.9
Signals
EFLPTOC Input signals
Table 506: EFLPTOC Input signals
Name
Type
Default
Description
IRES
SIGNAL
-
Residual current
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
ENA_MULT
BOOLEAN
0=False
Enable signal for cur-
rent multiplier
1MRS759142 F
Protection functions
REX640
Technical Manual
445
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......