Self-supervision
Each input contains functionality to monitor the input measurement chain. The
circuitry monitors the RTD channels continuously and reports a circuitry break of
any enabled input channel. If the measured input value is outside the limits, the
minimum/maximum value is shown in the corresponding output. The quality of the
corresponding output is set accordingly, and the fault is reported at
SENSOR_FLT
to
indicate misbehavior in the mA/RTD input.
Table 103: Limits for the mA/RTD inputs
mA/RTD input
Limit value
RTD temperature, high
> 200°C
RTD temperature, low
< –40°C
mA current, high
> 24 mA
mA current, low
< –24 mA
Resistance, high
> 4000 Ω
Resistance, low
Not defined
1
When necessary, the valid measuring range may be narrower than the default of the
selected measuring range. A narrower range can be defined with the
Value minimum
and
Value maximum settings.
RTD input supervision
RTD sensor currents are measured continuously at a fixed rate. The delay between
the RTD current/connectivity checks is about 10s at a maximum (if all 10 RTD
channels are active). If the RTD current is not within ±5% of the expected current,
the measurement is considered to be invalid, and the channel is discarded until a
valid current is obtained.
The expected currents are 1 mA for RTD sensors and 0.21 mA for pure resistance.
While the quality of the invalid input is set accordingly, a warning is also provided on
the Relay Status page of LHMI/WHMI. The invalid signal is deactivated as soon as
the corresponding input signal is within the valid range.
Delay for
SENSOR_FLT
activation depends on the connected sensor type,
amount of connected channels and RTD module type. The maximum
delay is 10 seconds.
mA input supervision
The current limit for mA input supervision is defined by parameter
Sensor fault
level. Value must be below Input minimum parameter.
SENSOR_FLT
is activated,
and measurement quality is set bad when measured current is below set limit. The
supervision is disabled if
Sensor fault level is set to 0 mA.
3.15.3.2
Output mode
A measurement value from another function, mA input or RTD input can be
represented by the mA output. The mA output scaling principle is otherwise similar
1
Low limit is not defined for the resistance input. In practice the low limit is 0 because the
resistance cannot be negative.
1MRS759142 F
Basic functions
REX640
Technical Manual
173
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......