for the underfrequency can be set from a few seconds to a few fractions of a second
stepwise from a higher frequency value to a lower frequency value.
Table 893: Setting for a five-step underfrequency operation
Load-shedding steps
Start value Freq setting
Operate Tm Freq setting
1
0.984 · Fn (49.2 Hz)
45000 ms
2
0.978 · Fn (48.9 Hz)
30000 ms
3
0.968 · Fn (48.4 Hz)
15000 ms
4
0.958 · Fn (47.9 Hz)
5000ms
5
0.950 · Fn (47.5 Hz)
500 ms
The rate of change of frequency function is not instantaneous since the function
needs time to supply a stable value. It is recommended to have a time delay long
enough to take care of the signal noise.
Small industrial systems can experience the rate of change of frequency as high
as 5 Hz/s due to a single event. Even large power systems can form small islands
with a large imbalance between the load and generation when severe faults or
combinations of faults are cleared. Up to 3 Hz/s has been experienced when a small
island becomes isolated from a large system. For normal severe disturbances in
large power systems, the rate of change of the frequency is much less, often just a
fraction of 1.0 Hz/s.
Similarly, the setting for df/dt can be from 0.1 Hz/s to 1.2 Hz/s in steps of 0.1 Hz/s
to 0.3 Hz/s for large distributed power networks, with the operating time varying
from a few seconds to a few fractions of a second. Here, the operating time should
be kept in minimum for the higher df/dt setting.
Table 894: Setting for a five-step df/dt< operation
Load-shedding steps
Start value df/dt setting
Operate Tm df/dt setting
1
-0.005 · Fn /s (-0.25 Hz/s)
8000 ms
2
-0.010 · Fn /s (-0.50 Hz/s)
2000 ms
3
-0.015 · Fn /s (-0.75 Hz/s)
1000 ms
4
-0.020 · Fn /s (-1.00 Hz/s)
500 ms
5
-0.025 · Fn /s (-1.25 Hz/s)
250 ms
Once the frequency has stabilized, the shed load can be restored. The restoring
operation should be done stepwise, taking care that it does not lead the system
back to the emergency condition.
Table 895: Setting for a five-step restoring operation
Load-shedding steps
Restore start Val setting
Restore delay time setting
1
0.990 · Fn (49.5 Hz)
200000 ms
2
0.990 · Fn (49.5 Hz)
160000 ms
3
0.990 · Fn (49.5 Hz)
100000 ms
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
937
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......