Description
Type test value
Reference
Damped oscillatory magnetic
field immunity test
• 2 s
• 1 MHz
100 A/m
400 transients/s
IEC 61000-4-10
Voltage dips and short inter-
ruptions
0%/50 ms Criterion A
40%/200 ms Criterion C
70%/500 ms Criterion C
0%/5000 ms Criterion C
IEC 61000-4-11
IEC 61000-4-29
IEC 60255-26
Power frequency immunity
test
• Common mode
• Differential mode
Binary inputs only 300 V rms
150 V rms
IEC 61000-4-16
IEC 60255-26, class A
Emission tests
• Conducted
0.15. 0.50 MHz
0.5...30 MHz
• Radiated
30...230 MHz
230...1000 MHz
1…3 GHz
3…6 GHz
<79 dB (µV) quasi peak
<66 dB (µV) average
<73 dB (µV) quasi peak
<60 dB (µV) average
<40 dB (µV/m) quasi peak,
measured at 10 m distance
<47 dB (µV/m) quasi peak,
measured at 10 m distance
<76 dB (µV/m) peak
<56 dB (µV/m) average,
measured at 3 m distance
<80 dB (µV/m) peak
<60 dB (µV/m) average,
measured at 3 m distance
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
Table 1688: Safety-related tests
Description
Type test value
Reference
Overvoltage category
III
IEC 60255-27
Pollution degree
2
IEC 60255-27
Insulation class
Class I
IEC 60255-27
Dielectric tests
500 V, 50 Hz, 1 min, RS-485
and IRIG-B
1 kV, 50 Hz, 1 min, across
open contacts
1.5 kV, 50 Hz, 1 min, Ethernet
RJ-45
IEC 60255-27
Table continues on the next page
Protection relay and functionality tests
1MRS759142 F
1950
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......