Parameter
Values (Range)
Unit
Step
Default
Description
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in
IDMT curves
End section 1
0...200
%Ir
1
100
Turn-point between
the first and the
second line of
the operating char-
acteristics
Slope section 2
10...50
%
1
50
Slope of the second
line of the operat-
ing characteristics
End section 2
200...2000
%Ir
1
500
Turn-point between
the second and the
third line of the op-
erating characteris-
tics
Slope section 3
10...200
%
1
150
Slope of the third
line of the operat-
ing characteristics
Operating curve
type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
15=IEC Def. Time
Selection of time
delay curve for sta-
bilized stage
Operate delay time 45...200000
ms
1
45
Operate delay time
for stabilized stage
Table 650: LNPLDF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
4=test/blocked
5=off
1=on
Operation mode of
the function
Winding selection
1=Not in use
2=Winding 1
3=Winding 2
1=Not in use
IED location re-
spect to transform-
er, HV (Winding 1)
side or LV (Winding
2) side
Winding 1 type
1=Y
2=YN
3=D
4=Z
5=ZN
1=Y
Connection of the
HV side windings
Winding 2 type
1=y
2=yn
3=d
4=z
5=zn
1=y
Connection of the
LV side windings
Clock number
0=Clk Num 0
1=Clk Num 1
2=Clk Num 2
4=Clk Num 4
5=Clk Num 5
6=Clk Num 6
7=Clk Num 7
0=Clk Num 0
Setting the phase
shift between HV
and LV with clock
number for connec-
tion group com-
pensation (e.g.
Dyn11 -> 11)
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
677
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......