
feeder. This is achieved by allowing a time-delayed overreaching zone to trip
instantaneously when a fault occurs. For this purpose, one of the DSTPDIS zones
can be configured with an independently set reach.
After the overreaching zone instantaneously trips, the autoreclosing sequence
starts. If the fault is transient, the system may get restored in the first shot of
AR. However, in case of a persistent fault only the first trip of the AR sequence
is accelerated by Zone extension logic. During the rest of the sequence, Zone
extension logic is blocked and AR initiation is performed selectively by the time-
graded distance zones.
If the fault is located on the adjacent feeder or bus within the reach of
the overreaching zone, tripping and AR initiation take place in an external
fault.
Zone extension logic can be described using a module diagram.
EX_ACC
AR_READY
NONDIR_ST
BLOCK
OPR_Z_EXTN
AR control
Zone
acceleration
Figure 700: Functional module diagram of Zone extension logic
AR control
The AR control module supervises the zone acceleration by monitoring the status
of the
AR_READY
and
NONDIR_ST
input signals. The
READY
output signal from
the autorecloser (AR) function, which indicates the status of the autoreclosing, is
connected to the
AR_READY
input. The start signal from the non-directional zone is
connected to the
NONDIR_ST
input. If the non-directional zone is not available for
this, then the start output from the overreaching zone with the biggest reach or
GFC can be used instead.
The permission for zone acceleration is given if
AR_READY
= TRUE, that is, the AR
function is ready to start a new AR sequence. If the set reclaim time of the AR
function expires before the fault is cleared, the
NONDIR_ST
input signal is used
to block the activation of the zone acceleration. This ensures that the accelerated
trip followed by the AR initiation is not repeated for the same fault regardless of
the reclaim time setting and the reach of the overreaching zone connected to the
EX_ACC
input. Otherwise, this could lead to pumping of the circuit breaker, that
is, the repetition of the first shot without being able to complete the desired AR
sequence.
The AR control module blocks the Zone acceleration module after the
initiation of the first shot until the AR sequence has been completed, that
is, until the
AR_READY
input signal changes its state back from FALSE to
TRUE.
Zone acceleration
The start signal from the overreaching zone whose operation is to be accelerated
is connected to the
EX_ACC
input. When the
EX_ACC
input is activated and,
simultaneously, the AR control module gives permission for acceleration, the
Protection related functions
1MRS759142 F
1232
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......