6.7.3
Functionality
The motor start counter function MSCPMRI counts the number of motor starts
and distinguishes between cold and warm starts. The allowed number is generally
provided by the motor manufacturer. The motor starting
MOT_START
output of the
motor start-up supervision function is used to count the starts. The motor thermal
level
TEMP_RL
calculated by the thermal overload protection is used to distinguish
between a cold and warm start.
The function contains a blocking functionality. It is possible to block the function
outputs or the function itself.
6.7.4
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "on" and "off".
The operation of MSCPMRI can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
BLOCK
OPERATE
BLK_RESTART
MOT_RUN
Motor start
counter
RESET
Limit
supervision
TEMP_RL
START_EMERG
Figure 763: Functional module diagram
Motor start counter
This module counts the number of motor starts. The value of the cold count
COLD_COUNT and warm count WARM_COUNT is available in the Monitored data
view. On the rising edge of
MOT_RUN
, the module increments the cold start counter.
If the thermal content available at the
TEMP_RL
input is above the set
Warm start
level when the rising edge of the
MOT_RUN
input is received, both cold and warm
start counter values are incremented.
If
Operation of the thermal overload protection for motors function
MPTTR is set as "Off", the
TEMP_RL
value is not available. In this case,
the warm start counter does not increase.
The counter decrease timer also starts at the first increment of the cold start
counter (that is the first time when the counter increases from zero). When
Cnt
decrease time elapses, both cold and warm start counters decrease by one and the
counter decrease timer restarts. This is repeated until both cold and warm counters
are zero.
When the motor is not in operation, that is, the motor is in stop condition, it takes
more time to cool. During such condition
Cnt decrease time is multiplied by a Cnt
Dec timer Mult setting.
The motor start detection is available at the
MOT_START
output of the motor
start-up supervision function STTPMSU. The
MOT_START
output of STTPMSU must
be connected to the
MOT_RUN
input of this function in Application Configuration
1MRS759142 F
Supervision functions
REX640
Technical Manual
1343
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......