inaccuracies, variations in tap changer position (if not compensated), transformer
no-load current and instantaneous transformer inrush currents. An increase in the
load current causes the differential current, caused by the CT inaccuracies and the
tap changer position, to grow at the same percentage rate.
In a biased differential protection relay in normal operation or during external faults,
the higher the load current is the higher is the differential current required for
tripping. When an internal fault occurs, the currents on both sides of the protected
object are flowing into it. This causes the biasing current to be considerably smaller,
which makes the operation more sensitive during internal faults.
I
I
I
b
W
W
=
−
1
2
2
(Equation 158)
If the biasing current is small compared to the differential current or if the phase
angle between the winding 1 and winding 2 phase currents is close to zero
(in a normal situation, the phase difference is 180 degrees), a fault has most
certainly occurred in the area protected by the differential protection relay. Then
the operation value set for the instantaneous stage is automatically halved and the
internal blocking signals of the biased stage are inhibited.
Transformer vector group matching
The phase difference of the winding 1 and winding 2 currents that is caused
by the vector group of the power transformer is numerically compensated. The
matching of the phase difference is based on the phase shifting and the numerical
delta connection inside the protection relay. The
Winding 1 type parameter
determines the connection on winding 1 (”Y”, ”YN”, ”D”, ”Z”, ”ZN”). The
Winding 2
type parameter determines the connections of the phase windings on the low
voltage side (“y”, ”yn”, ”d”, ”z”, ”zn”).
The vector group matching can be implemented either on both, winding 1 and
winding 2, or only on winding 1 or winding 2, at intervals of 30° with the
Clock
number setting.
When the vector group matching is Yy0 and the
CT connection type is according to
"Type 2", the phase angle of the phase currents connected to the protection relay
does not change. When the vector group matching is Yy6, the phase currents are
turned 180° in the protection relay.
Example 1
Vector group matching of a Ynd11-connected power transformer on winding
1,
CT connection type according to type 1. The Winding 1 type setting
is ”YN”,
Winding 2 type is “d” and Clock number is “Clk Num 11”. This is
compensated internally by giving winding 1 internal compensation value
+30° and winding 2 internal compensation value 0°:
1MRS759142 F
Protection functions
REX640
Technical Manual
683
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......