I_COM_ANGL_B
~+60°
Phase B - Branch 1 or Phase B
- Branch 4
I_COM_ANGL_B
~–120°
Phase B - Branch 2 or Phase B
- Branch 3
I_COM_ANGL_C
~–60°
Phase C - Branch 1 or Phase C
- Branch 4
I_COM_ANGL_C
~+120°
Phase C - Branch 2 or Phase C
- Branch 3
If external fuses are used, the direction of an unbalance current is opposite to that
of the bank where internal fuses are in use.
Table 1078: Detection of element failure location for external fuse capacitor bank
Name of the phase angle
Phase angle of unbalance cur-
rent
Element failure branch loca-
tion
I_COM_ANGL_A
~0°
Phase A - Branch 1 or Phase A
- Branch 4
I_COM_ANGL_A
~+180°
Phase A - Branch 2 or Phase A
- Branch 3
I_COM_ANGL_B
~–120°
Phase B - Branch 1 or Phase B
- Branch 4
I_COM_ANGL_B
~+60°
Phase B - Branch 2 or Phase B
- Branch 3
I_COM_ANGL_C
~+120°
Phase C - Branch 1 or Phase C
- Branch 4
I_COM_ANGL_C
~–60°
Phase C - Branch 2 or Phase C
- Branch 3
Level detector 1
The phasewise-compensated unbalance currents
I_COM_AMPL_A
,
I_COM_AMPL_B
and
I_COM_AMPL_C
are compared to the set
Start value. If the compensated
unbalance current in one or more phases exceeds the set
Start value, the Level
detector 1 module sends the enabling signal to the Timer 1 module.
Timer 1
Once activated, the Timer 1 module activates the
START
output. Depending on the
value of the
Operating curve type setting, the time characteristics are according
to DT or IDMT. When the operation timer has reached the value of
Operate delay
time in the DT mode or the maximum value defined by the inverse time curve, the
OPERATE
output is activated.
When the user-programmable IDMT curve is selected, the operation time
characteristics are defined by the parameters
Curve parameter A, Curve parameter
B, Curve parameter C and Curve parameter E.
In a drop-off situation, that is, when a fault suddenly disappears before the
operation delay is exceeded, the Timer 1 reset state is activated. The functionality
of Timer 1 in the reset state depends on the combination of the
Operating curve
type and Reset delay time settings. When the DT characteristic is selected, the reset
timer runs until the set
Reset delay time value is exceeded. When the IDMT curves
1MRS759142 F
Protection functions
REX640
Technical Manual
1135
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......