The maximum percentage length of the potentiometer gap can be set with setting
Pot Max gap. The controller determines a gap length by measuring the distance
between both ends of a gap in ohms. A gap is indicated when the ohmic position
exceeds 2000 Ω.
If the coil potentiometer enters a gap during the normal operation, the controller
estimates the coil position based on its previous known position and coil movement
speed. If the actual gap length exceeds the setting
Pot Max gap or a new
gap appears during daily operation,
POT_ALARM
output is activated. Moreover,
TUNING_STS monitored data indicates the reason of alarm. High values of the
Pot
Max gap setting introduce inaccuracy to the coil movement as the coil position is
based on a calculated estimate. The purpose of the gap detection functionality is
to enable the controller operation even if the potentiometer is worn out during the
normal operation. The potentiometer should be replaced during the next service
break in order to guarantee accurate operation of the controller. The gap detection
functionality can be disabled by setting the
Pot Max gap value to 0. Potentiometer
gaps are illustrated in
.
Potentiometer
value [Ω]
Potentiometer
relative position [%]
Gap length
0
100
min
max
Figure 930: Potentiometer gaps
9.11.9
Signals
9.11.9.1
PASANCR Input signals
Table 1592: PASANCR Input signals
Name
Type
Default
Description
IRES
SIGNAL
-
Residual current
U3P
SIGNAL
-
Three-phase voltages
URES
SIGNAL
-
Residual voltage
Table continues on the next page
1MRS759142 F
Control functions
REX640
Technical Manual
1747
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......