The use of wattmetric protection gives a possibility to use the dedicated inverse
definite minimum time characteristics. This is applicable in large high-impedance
earthed networks with a large capacitive earth-fault current.
In a network employing a low-impedance earthed system, a medium-size neutral
point resistor is used. Such a resistor gives a resistive earth-fault current
component of about 200...400 A for an excessive earth fault. In such a system,
the directional residual power protection gives better possibilities for selectivity
enabled by the inverse time power characteristics.
4.2.7.9
Signals
WPWDE Input signals
Table 595: WPWDE Input signals
Name
Type
Default
Description
IRES
SIGNAL
-
Residual current
URES
SIGNAL
-
Residual voltage
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
RCA_CTL
BOOLEAN
0=False
Relay characteristic
angle control
WPWDE Output signals
Table 596: WPWDE Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.2.7.10
WPWDE Settings
Table 597: WPWDE Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Directional mode
2=Forward
3=Reverse
2=Forward
Directional mode
Current start value 0.010...5.000
xIn
0.001
0.010
Minimum operate
residual current for
deciding fault di-
rection
Voltage start value 0.010...1.000
xUn
0.001
0.010
Start value for re-
sidual voltage
Power start value
0.003...1.000
xSn
0.001
0.003
Start value for re-
sidual active power
Reference power
0.050...1.000
xSn
0.001
0.150
Reference value of
residual power for
Wattmetric IDMT
curves
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
539
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......