Timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is
available in the Monitored data view.
Blocking logic
The binary input
BLOCK
can be used to block the function. The activation of the
BLOCK
input deactivates all outputs and resets internal timers.
4.5.4.6
Application
A sudden power loss, tap changer regulating failures and open line ends on long
lines are abnormal conditions which cause overvoltage in a power system. PSPTOV
is applied to power system elements, such as generators, transformers, motors and
power lines, to detect overvoltage conditions.
PSPTOV can be used in combination with low-current signals or a directional
reactive overpower function to identify the distribution line with an open remote
end. PSPTOV can also be used to initiate voltage correction measures, such as
insertion of shunt reactors or switching out capacitor banks, to control the voltage.
Overvoltage faced by the power transformer can lead to an overexcitation problem.
Overexcitation normally occurs when the voltage-to-frequency ratio increases much
above the design value resulting into transformer operation under a nonlinear
region. A transformer can be in such an overvoltage situation during a sudden loss
of load due to underfrequency load shedding. Overexcitation results in an increase
of the exciting current which leads to core heating and thus to transformer damage.
PSPTOV along with the underfrequency protection can be used for the protection of
the transformer during overexcitation.
Some common reasons leading to positive-sequence overvoltages are:
• Broken conductor falling to a crossing overhead line, transformer flash overfault
from high-voltage winding to low-voltage winding
• Malfunctioning of a voltage regulator or wrong settings under manual control
(symmetrical voltage increase)
• Low load compared to the reactive power generation (symmetrical voltage
increase)
PSPTOV prevents sensitive equipment from running under overvoltage conditions
which cause equipment overheating or stress on insulation material.
4.5.4.7
Signals
PSPTOV Input signals
Table 814: PSPTOV Input signals
Name
Type
Default
Description
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
1MRS759142 F
Protection functions
REX640
Technical Manual
873
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......