Figure 306: Definition of the relay characteristic angle
The phase angle difference is calculated based on the
Characteristic angle setting
(also known as Relay Characteristic Angle (RCA) or Relay Base Angle or Maximum
Torque Angle (MTA)). The
Characteristic angle setting is done based on the method
of earthing employed in the network. For example, in case of an unearthed network,
the
Characteristic angle setting is set to -90°, and in case of a compensated
network, the
Characteristic angle setting is set to 0°. In general, Characteristic
angle is selected so that it is close to the expected fault angle value, which results
in maximum sensitivity.
Characteristic angle can be set anywhere between -179°
to +180°. Thus, the effective phase angle (
ϕ
) for calculating the residual power
considering characteristic angle is according to the equation.
φ
= ∠ −
− ∠
−
(
)
(
)
Uo
Io Characteristic angle
(Equation 75)
In addition, the characteristic angle can be changed via the control signal
RCA_CTL
.
The
RCA_CTL
input is used in the compensated networks where the compensation
coil sometimes is temporarily disconnected. When the coil is disconnected, the
compensated network becomes isolated and the
Characteristic angle setting must
be changed. This can be done automatically with the
RCA_CTL
input, which results
in the addition of -90° in the
Characteristic angle setting.
The value (ANGLE_RCA) is available in the monitored data view.
Protection functions
1MRS759142 F
532
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......