Figure 718: Functional module diagram of weak-end infeed logic
The WEI logic is enabled using the
Wei mode setting.
• If
Wei mode= "Off", the WEI logic is disabled.
• If
Wei mode= "Echo", the WEI logic is enabled without Level detector.
• If
Wei mode= "Echo and Operate", the WEI logic is enabled with Level detector.
Level detector
Both phase-to-earth and phase-to-phase voltages are monitored. The undervoltage
criteria are applied to the phase-to-phase voltages with the
PPV level for Wei setting
and to the phase-to-earth voltages with the
PhV level for Wei. Level detector sends
an enable signal for a phase to Weak-end trip logic when one or more voltages
are below the corresponding settings. Level detector blocks the enable signal if all
three-phase voltages are above the set value more than 100 ms. This is to avoid
sending an unnecessary operate signal if the breaker is already open.
Echo logic
Echo logic returns the received carrier signal with the
ECHO
output when it receives
a
CR
signal if no fault has been detected by the forward- and reverse-looking zones
and the duration of
CR
is longer than the coordination time delay (setting
Wei Crd
time). The received carrier receive signal is also given as the
CR
output.
When the WEI logic is enabled at both feeder ends, a spurious signal
can be looped round by Echo logic. To avoid a continuous lockup of the
system, the duration of the echoed signal is limited to 200 ms.
The
ECHO
and
CR
outputs can be blocked by activating the
BLOCK
input. The
FF
,
BLK_WEI1
and
BLK_WEI2
inputs can be used to block the
ECHO
output. The
FF
input is usually connected to the functional output of the fuse failure function,
and the
BLK_WEI1
input is typically connected to the start signals of the forward
and reverse directional residual overcurrent functions within the terminal. The
BLK_WEI2
signal has an in-built 200 ms drop-off delay. The
BLK_WEI2
input is
usually connected to all the fault detection functions within the terminal except
the residual overvoltage function.
Protection related functions
1MRS759142 F
1268
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......