IRIG-B
IRIG-B time synchronization requires IRIG-B format B00x and IRIG-B time code
extensions according to IEEE Std C37.118.1TM-2011. The extensions are defined by
Annex D.
The synchronization time in IRIG-B can be either UTC time or local time. As no
reboot is necessary, the time synchronization starts immediately after the IRIG-
B synchronization source is selected and the IRIG-B signal source is connected.
GNRLLTMS signals reflect the signal status from the IRIG-B master.
IRIG-B time synchronization requires a COM module with an
IRIG-B
input.
DNP3, Modbus, IEC 60870-5-101/104 and IEC 60870-5-103
For legacy protocols as synchronization source, a timeout can be set by
Time
Syn Src Tmm (minutes). This setting defines the maximum interval required
by the protocol master sending the time synchronization commands. If a time
synchronization command has not been received from the protocol master during
this period, bad synchronization status is raised for the protection relay.
Legacy protocols as time synchronization sources do not offer the best
accuracy. For better accuracy PTP, SNTP or IRIG-B time synchronization is
recommended.
3.6.1.3
Signals
Table 50: GNRLLTMS Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm status for clock synchronization Al-
ways FALSE with
Synch source
set to "None".
WARNING
BOOLEAN
Warning status for clock synchronization Al-
ways FALSE with
Synch source
set to "None".
EXTCLKMSTR
BOOLEAN
Status of the protection relay's clock syn-
chronization Always FALSE with
Synch source
set to "None".
Table 51: SNTP Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm status for clock synchronization TRUE
if the connection to both primary and secon-
dary SNTP servers has been lost. FALSE if the
connection to the secondary SNTP server is
detected.
WARNING
BOOLEAN
Warning status for clock synchronization
TRUE if the connection to SNTP primary serv-
er has been lost. Otherwise FALSE.
EXTCLKMSTR
BOOLEAN
Status of the protection relay's clock syn-
chronization.
TRUE if the protection relay has been
synchronized by an SNTP server.
1MRS759142 F
Basic functions
REX640
Technical Manual
125
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......