An example of the feature is shown in
where the initial coil position
is at 60 A, the parallel resistor is disconnected and the target position is at 110
A. Before the controller starts moving the coil, it estimates if the zero-sequence
voltage at target position is below the
V Res maximum setting and if the movement
is allowed. If the conditions allow, the controller starts moving the coil towards the
higher current. While the movement stops at
V Res maximum (set to 3.5 percent
of the system's nominal phase-to-earth voltage in this example), the controller
automatically connects the parallel resistor and moves the coil to the desired
inductive current position (that is, 110 A). After the coil has reached the target
position, the controller automatically disconnects the resistor, that is, returns it to
its original connection state while simultaneously obtaining the target position of
110 A with the parallel resistor disconnected.
20
40
60
80
100
120
140
Coil inductive current [A]
Uo
[%]
1
1.5
2.0
2.5
3.0
3.5
4.0
4.5
V Res maximum
Resistor
OFF
Resistor
ON
Ini
ti
a
l position =
60
A
Target
position
=
110A
Figure 927: Damping of the resonance curve by using the parallel resistor
The number of maximum tuning cycles can be limited with
Tuning cycles setting.
The delay between consecutive tuning cycles is controllable by setting
Tuning cycles
delay. After the maximum number of tuning cycles is reached, the tuning procedure
can be started by activating the
ST_TUNING
input, for example, via HMI application.
The counter for maximum tuning cycles is reset after a successful tuning operation.
The
ALARM
output is a general problem indication during the tuning process.
Usually, it is an indication of not obtaining a required minimum level or change
of zero-sequence voltage during the coil movement. The reason for this might be,
for example, a very symmetrical network. Other reasons for the
ALARM
indication
are coil movement into wrong direction, maximum number of tuning sequences
exceeded or simultaneous indication from both end switches of the coil. There is a
dedicated
MOT_ALARM
output indicating no detected coil movement after activating
RAISE_OWN
or
LOWER_OWN
outputs.
After
ALARM
indication with ALARM_STS “Umin not reached” or “Cannot obtain
minimum Uo variation” the coil is moved to a position which is defined with
Error
Control functions
1MRS759142 F
1740
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......