phase difference to the voltages between the high- and low-voltage sides. The angle
adjustment can be used to meet synchronism.
The vector group of the power transformer is defined with clock numbers, where
the value of the hour pointer defines the low-voltage side phasor and the high-
voltage side phasor is always fixed to the clock number 12, which is the same
as zero. The angle between clock numbers is 30º. When comparing phase angles,
the
U_BUS
input is always the reference. This means that when the Yd11 power
transformer is used, the low-voltage side voltage phasor leads the high-voltage side
phasor by 30º or lags by 330º. The rotation of the phasors is counterclockwise.
The generic rule is that a low-voltage side phasor lags the high-voltage side phasor
by clock number · 30º. This is called angle difference adjustment and can be set for
ASGCSYN with the
Phase shift setting.
9.6.7
Signals
9.6.7.1
ASGCSYN Input signals
Table 1519: ASGCSYN Input signals
Name
Type
Default
Description
U3P1
SIGNAL
-
Three-phase voltages
(generator side)
U3P2
SIGNAL
-
Three-phase voltages
(bus side)
BLOCK
BOOLEAN
0=False
Blocking signal of the
auto synchronization
function
CL_COMMAND
BOOLEAN
0=False
External closing re-
quest
EXT_CHECK
BOOLEAN
0=False
External permissive
check for CB close
BYPASS
BOOLEAN
0=False
Request to bypass
synchronism check
and voltage check
GCB_TEST
BOOLEAN
0=False
Circuit breaker test
position status
GCB_CLOSE
BOOLEAN
0=False
Circuit breaker close
status
GCB_OPEN
BOOLEAN
0=False
Circuit breaker open
status
ISO_A_CLOSE
BOOLEAN
0=False
Isolator A close sta-
tus
ISO_B_CLOSE
BOOLEAN
0=False
Isolator B close sta-
tus
Table continues on the next page
Control functions
1MRS759142 F
1580
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......